GSO IEC 61238-1-3:2021

IEC 61238-1-3:2018
Gulf Standard   Current Edition · Approved on 01 July 2021

Compression and mechanical connectors for power cables - Part 1-3: Test methods and requirements for compression and mechanical connectors for power cables for rated voltages above 1 kV (U<sub>m</sub> = 1,2 kV) up to 30 kV (U<sub>m</sub> = 36 kV) tested on non-insulated conductors

GSO IEC 61238-1-3:2021 Files

GSO IEC 61238-1-3:2021 Scope

IEC 61238-1-3:2018 applies to compression and mechanical connectors for power cables for rated voltages above 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), for example buried cables or cables installed in buildings, having
a) conductors complying with IEC 60228 having nominal cross-sectional areas between 2,5 mm2 and 1 200 mm2 for copper and between 16 mm2 and 1 200 mm2 for aluminium, excluding Milliken conductors;
b) a maximum continuous conductor temperature not exceeding 90 °C.
This document is not applicable to connectors for overhead line conductors nor to connectors with a sliding contact.
The object of this document is to define the type test methods and requirements which apply to compression and mechanical connectors for power cables with copper or aluminium conductors. The reference method is to perform the tests on unused conductors.
This first edition, together with IEC 61238-1-1 and IEC 61238-1-2, cancels and replaces IEC 61238-1:2003.
This edition includes the following significant technical changes with respect to IEC 61238­-1:2003:
a) The scope has been widened to cover connectors for conductors from 10 mm2 down to 2,5 mm2 and has been limited to 1 200 mm2 for connectors for copper and aluminium conductors because test experience and applications are rare for conductors of larger cross-sectional areas.
b) A new mechanical class has been introduced to satisfy the demand for connectors subjected to higher mechanical forces than those specified in Class 1 for conductors of larger cross-sectional areas.
c) For the electrical test, a maximum elevated heating current has been set in order to avoid unrealistic current densities during the test which may change the properties of tested connectors.
d) For the short-circuit test, the method of calculation and requirements have been updated.
e) For the mechanical test, the methods and requirements have been updated.
f) A proposal for an electrical test on cable terminal lugs for application in separable connectors has been introduced.

Best Sellers From Electrical Sector

GSO 2530:2016
 
Gulf Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 2530:2016
GSO 2530:2016 
Omani Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 34:2007
GSO 34:2007 
Omani Standard
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES
GSO 34:2007
 
Gulf Technical Regulation
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES

Recently Published from Electrical Sector

GSO IEC 61558-2-2:2024
IEC 61558-2-2:2022 
Gulf Standard
Safety of transformers, reactors, power supply units and combinations thereof - Part 2-2: Particular requirements and tests for control transformers and power supply units incorporating control transformers
GSO IEC 60664-1:2024
IEC 60664-1:2020 
Gulf Standard
Insulation coordination for equipment within low-voltage supply systems - Part 1: Principles, requirements and tests
GSO IEC 61936-2:2024
IEC 61936-2:2023 
Gulf Standard
Power installations exceeding 1 kV AC and 1,5 kV DC - Part 2: DC
GSO IEC TS 62915:2024
IEC TS 62915:2023 
Gulf Standard
Photovoltaic (PV) modules - Type approval, design and safety qualification - Retesting