GSO IEC 60332-3-24:2021

IEC 60332-3-24:2018
Gulf Standard   Current Edition · Approved on 01 July 2021

Tests on electric and optical fibre cables under fire conditions - Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C

GSO IEC 60332-3-24:2021 Files

English 28 Pages
Current Edition Reference Language

GSO IEC 60332-3-24:2021 Scope

IEC 60332-3-24:2018 RLV contains both the official IEC International Standard and its Redline version. The Redline version is not an official document, it is available in English only and provides you with a quick and easy way to compare all the changes between the official IEC Standard and its previous edition.

IEC 60332-3-24:2018 covers category C for methods of test for the assessment of vertical flame spread of vertically mounted bunched wires or cables, electrical or optical, under defined conditions. This document relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 1,5 l/m of test sample. The flame application time is 20 min. The method of mounting uses the front of the standard ladder. The category is intended for general use where low volumes of non-metallic material are required to be evaluated. The test is intended for type approval testing. The requirements for the selection of cables for testing are given in Annex A. The flame spread is measured as the extent of damage of the cable sample. This procedure can be used to demonstrate the cable’s ability to limit flame spread. A recommended performance requirement is given in Annex B. This second edition cancels and replaces the first edition published in 2000 and Amendment 1:2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) adjustments have been made to the title, and elsewhere, to emphasise the standard is applicable to optical fibre cables as well as metallic conductor types;
b) details of the way in which cables are mounted on the ladder have been better defined in order to improve repeatability and reproducibility.
It has the status of a group safety publication in accordance with IEC Guide 104.
The contents of the interpretation sheet 1 of January 2019 have been included in this copy.

Best Sellers From Electrical Sector

GSO 2530:2016
 
Gulf Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 2530:2016
GSO 2530:2016 
Omani Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 34:2007
GSO 34:2007 
Omani Standard
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES
GSO 34:2007
 
Gulf Technical Regulation
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES

Recently Published from Electrical Sector

GSO 2770:2024
 
Gulf Standard
WATER HEATERS - ENERGY PERFORMANCE REQUIREMENTS
GSO IEC TS 62257-4:2024
IEC TS 62257-4:2015 
Gulf Standard
Recommendations for renewable energy and hybrid systems for rural electrification - Part 4: System selection and design
GSO IEC 61968-13:2024
IEC 61968-13:2021 
Gulf Standard
Application integration at electric utilities - System interfaces for distribution management - Part 13: Common distribution power system model profiles
GSO IEC 62246-4:2024
IEC 62246-4:2023 
Gulf Standard
Reed switches – Part 4: Application in conjunction with magnetic actuator used for magnetic sensing devices